Articles
January 30, 2025
Meeting Summary - 11/14/24 PRS Meeting
1 – Antitrust Admonition – Diana Coleman
2 – Approval of Minutes – Vote – Diana Coleman
2.1 – October 17, 2024
- Motion to approve the October 17, 2024, PRS Meeting Minutes as presented added to the combo ballot.
3 – TAC Update – Diana Coleman
- TAC approved three proposals: NPRR1245, NPRR1197, and NPRR1249.
- NPRR1180 was tabled by TAC and will be reconsidered with PGRR107.
- TAC decision on NPRR1180 is pending until PGRR107 progresses.
4 – Project Update – Troy Anderson
prs_november_2024_project_update.pdf
- Major projects have been added back as requested.
- Working on FTE analysis for a future meeting.
- Ideas to improve capacity for revision requests are being considered.
- November updates: Second Part of 1205 and 1218 for the REC program went live, and Texas SET was smoothly implemented.
- NPRR1231 is going live tomorrow, as notified in market notices.
- December updates include: wrapping up NPRR1217, final piece of SCR799 relating to export functionality, and some RIOO updates in NPRR1184.
- PGRR082 part of December release; PGRR088 moved to January.
- Reporting on projects is aligned with Matt Mereness’ RTC reporting.
- Major project slide updated for RTC go live in late 2025, and stabilization into 2026.
- NPRR1023 with CRR on hold for process improvements.
- Discussion about future projects DRRS and PCM, less resource demanding compared to RTC.
- NPRR1219 concerning CDR not explicitly noted; will be addressed offline.
- DRRS implementation project might start in Q4 2025, not going live then.
- December go-live target for NPRR945 on the 18th.
- Revised IAs and priorities/ranks posted for discussion in future agenda items.
- TWG meets monthly for technical discussions; technical teams are encouraged to participate.
- Acknowledgments for ERCOT and market participants for successfully implementing Texas SET.
5 – Review PRS Reports, Impact Analyses, and Prioritization – Vote – denotes no impact – Diana Coleman
- Four items are up for impact analysis and prioritization: items 1239 and 1240 have revised Impact Assessments.
- The goal is to move reports from the secure portion of ERCOT to the public-facing webpage.
5.1 – NPRR1239, Access to Market Information
- Motion to endorse and forward to TAC the 10/17/24 PRS Report and 10/29/24 Revised Impact for NPRR1239 with a recommended priority of 2025 and rank of 4540 added to the combo ballot.
- Costs for NPRR1239 and time requirements for project implementation were presented.
- Costs to build out APIs were removed to be aligned with other ERCOT API work in 2025 for efficiency.
- The initiative seeks to convert 63 reports from secure to public status.
- Implementation will depend on potential impacts with RTC, with hopes to progress in parallel.
- Priority was adjusted from 26 to 25, aiming for completion in 2025, with a consistent rank as both items will be handled together.
5.2 – NPRR1240, Access to Transmission Planning Information
- Motion to endorse and forward to TAC the 10/17/24 PRS Report and 10/29/24 Revised Impact for NPRR1240 with a recommended priority of 2025 and rank of 4540 added to the combo ballot.
- Discussion on combining NPRR1239 and NPRR1240 on the combo ballot.
- Consensus reached with no objections noted.
- Acknowledgment and confirmation to add items 1239 and 1240 to the meeting minutes.
5.3 – NPRR1246, Energy Storage Resource Terminology Alignment for the Single-Model Era*
- Motion to endorse and forward to TAC the 10/17/24 PRS Report and 7/31/24 Impact Analysis for NPRR1246 added to the combo ballot.
- Discussed NPRR1246 regarding Energy Storage Resource (ESR) terminology alignment.
- Preparation for RTC initiative scheduled for next year.
- No costs associated with the implementation.
- Previous unanimous vote to recommend language approval.
- Acknowledged amendments by September 20th ERCOT comments.
5.4 – NPRR1254, Modeling Deadline for Initial Submission of Resource Registration Data*
- Motion to endorse and forward to TAC the 10/17/24 PRS Report and 10/2/24 Impact Analysis for NPRR1254 added to the combo ballot.
- Final topic from ERCOT discussed was regarding the modeling deadline for initial submission of resource registration data.
- Proposal to modify the timeline by extending it one month.
- Purpose is to allow ERCOT and resource entities time to ensure submissions are error-free.
- No cost or project is associated with this change.
6 – Revision Requests Tabled at PRS
6.03 – NPRR1200, Utilization of Calculated Values for Non-WSL for ESRs
- Discussion on NPRR1200 focused on utilizing calculated values for non-wholesale storage load for Energy Storage Resources (ESRs).
- Item was previously discussed at the Wholesale Market Subcommittee (WMS) last week.
- A motion was made to revisit this item in the next month and to bring it to the Metering Working Group.
- The Metering Working Group has a scheduled meeting on the 20th where further discussions on NPRR1200 are expected to take place.
6.04 – NPRR1202, Refundable Deposits for Large Load Interconnection Studies
- WMWG has been reviewing this agenda item.
- Comments were filed after last month’s PRS meeting.
- Decision needed on whether those who filed comments want to address them or keep the item tabled.
- Reminder noted that if item remains tabled, no immediate action is required.
6.05 – NPRR1214, Reliability Deployment Price Adder Fix to Provide Locational Price Signals, Reduce Uplift and Risk
- CMWG is still reviewing NPRR1214 for an additional month.
- The item will be reconsidered by WMS in December.
- Joint comments were filed earlier in response to ERCOT’s August 9 comments.
6.06 – NPRR1226, Demand Response Monitor
- Technology Working Group will be addressing NPRR1226.
- Further discussions are expected in the next PRS meeting on NPRR1226.
6.07 – NPRR1229, Real-Time Constraint Management Plan Energy Payment
- Comments were filed on NPRR1229.
- Bill Barnes provided an update on agenda item 1202 and 1234.
- ERCOT expressed a desire to move forward with item 1234 while continuing to address concerns with 1202.
- Proposal to combine fee structures from Longhorn comments on 1202 with 1234.
- ERCOT is interested in the idea of combining components from the two.
- Comments have been shared with ERCOT staff regarding the potential combination.
- PRS members informed about the ongoing discussion regarding the integration of components.
6.08 – NPRR1234, Interconnection Requirements for Large Loads and Modeling Standards for Loads 25 MW or Greater
- ERCOT filed some comments earlier in the week regarding NPRR1234.
- Conversations about these comments are ongoing and expected to continue between 1202 and 1234.
6.09 – NPRR1235, Dispatchable Reliability Reserve Service as a Stand-Alone Ancillary Service
- NPRR1235 was initially tabled in June and referred to ROS and WMS.
- The item remains tabled at SAWG awaiting possible PUC discussion.
- The item is also still under discussion at WMS.
- Recent comments were filed by Luminant for NPRR1235.
- Ongoing discussions are taking place regarding NPRR1235.
6.10 – NPRR1238, Voluntary Registration of Loads with Curtailable Load Capabilities
- Comments were submitted by Steel Mills regarding the definition for VECL sat the end of last month.
- WMS may take action on these comments.
- Further developments are anticipated in December.
6.13 – NPRR1243, Revision to Requirements for Notice and Release of Protected Information or ECEII to Certain Governmental Authorities
- Motion to recommend approval of NPRR1243 as amended by the 10/10/24 ERCOT comments added to the combo ballot.
- Oncor filed comments proposing a streamlined notification process for ERCOT disclosures to FERC, NURC, and TRE.
- No new comments were filed on NPRR1243, and the committee considered moving the Oncor comments forward on a combo ballot.
- There was discussion about the language concerning compliance premiums not being awarded after December 31, 2024, and the potential need for an earlier effective date.
- Introduction of a new concept of a research and innovation partner by ERCOT, with suggestions to provide visibility into shared information via a website.
- Oncor’s initial concerns about transparency in information disclosure were addressed through a compromise solution.
- A suggestion was made to strike the use of ‘fax’ from notification methods, aligning with modern communication practices.
- Doug Fawn flagged a future NPRR to clean up standard form agreements regarding fax notification, projected for January.
6.14 – NPRR1247, Incorporation of Congestion Cost Savings Test in Economic Evaluation of Transmission Projects
- Motion to grant NPRR1247 Urgent status; to recommend approval of NPRR1247 as amended by the 11/11/24 ERCOT comments; and to forward to TAC NPRR1247 and the 8/9/24 Impact Analysis carries: 86% approval 13% opposition and 4 abstentions.
- NPRR1247 concerns a congestion cost savings test discussed extensively since it was filed in August.
- The proposal was approved at ROS with 11 abstentions and several no votes due to contentions over protocol references.
- ERCOT prefers revising the NPRR description rather than including references to two related white papers in protocol language.
- A special planning group workshop and several comments have been considered in the development of NPRR1247.
- Urgency is required to proceed with NPRR1247 due to its significant impact on congestion cost savings.
- Matt Arthur from ERCOT filed comments on Nov 11 recommending revisions in the revision description referring to two supporting white papers.
- ERCOT’s stance on white papers is that they are non-binding documents providing operational details without stakeholder approval, differing from binding protocol language.
- Martha Henson expressed support for keeping NPRR1247 out of protocol references and motioned for its urgency and approval, which was seconded.
- Comments were shared expressing concerns about the expedited process and potential suboptimal outcomes, including issues unresolved concerning the generation-load gap in models.
- Stakeholders expressed a desire for further discussion on related white papers, which ERCOT commits to addressing in future discussions.
6.15 – NPRR1250, RPS Mandatory Program Termination
- Motion to recommend approval of NPRR1250 as submitted added to the combo ballot.
- The item 1250 was tabled in September and referred to WMS, which unanimously endorsed it as submitted.
- Discussion was held about adding 1250 to the combat ballot.
- Concerns were raised about the effective date of the RPS program termination, with some feeling it needs to be sooner.
- The termination date of the RPS program is defined by HB1500, not ERCOT, and set for September 1st.
- Procedural steps for NPRR were discussed, with a hope for approval before September 1st.
- Concerns about confidentiality provisions not being removed before the program’s termination were addressed, emphasizing the importance of not exposing information before deletion of the program.
6.15b – NPRR1250, RPS Mandatory Program Termination
- Discussion on NPRR1250 regarding the termination of RPS Mandatory Program.
- Reference to compliance premiums will not be awarded after December 31, 2024, as stated in NPRR1218.
- NPRR1218 already includes the language regarding compliance premiums which is in force.
- Clarification and confirmation that NPRR1250’s language echoes NPRR1218.
- Addressed concerns related to repetition of language from NPRR1218.
- Explanation that NPRR1250’s language modifications will be “gray boxed” until September 1, 2025.
- Language about premiums expiring on December 31, 2027, is the new addition.
- Consensus to proceed with NPRR1250 in a combo ballot.
6.17 – NPRR1252, Pre-notice for Sharing of Some Information, Addition of Research and Innovation Partner, Clarifying Notice Requirements
- Motion to recommend approval of NPRR1252 as amended by the 11/8/24 ERCOT comments added to the combo ballot.
- Acknowledgment of pending cleanup next year.
- Mention of ERCOT’s November 8th comments regarding this item.
- Discussion on integrating NPRR1252 with the November 8th comments.
6.18 – NPRR1253, Incorporate ESR Charging Load Information into ICCP
- Motion to recommend approval of NPRR1253 as amended by the 10/10/24 ERCOT comments added to the combo ballot.
- WMSWG is still reviewing NPRR1253.
- The item was tabled last month to allow the sponsor time to file comments.
- Awaiting comments from the sponsor before proceeding.
6.19 – NPRR1255, Introduction of Mitigation of ESRs
- General agreement from past discussions to not implement until after RTC.
- For NPRR1255, Caitlin requested to table it due to a longer implementation outlook and agreed to provide more details by the next PRS meeting.
- There is consensus to keep NPRR1255 tabled until comments are filed or comfort with ERCOT is established.
- NPRR1253 was discussed within the Wholesale Market Working Group, but its official status is unclear as it is not tabled with ROS.
- TIEC had questions on NPRR1253 but is now open to moving it forward as their questions were addressed.
- NPRR1253 needs to be in effect by June 1, with a version of language recommended for approval.
- Discussion on NPRR1253 included the October 10th ERCOT comments related to Patterson and Company’s proposal, aiming to clean up references to prices and data.
- Further cost analysis for NPRR1253 to be done as indicated by Mr. Whitmire.
7 – Review of Revision Request Language – Vote – Diana Coleman
7.1 – NPRR1256, Settlement of MRA of ESRs
- Motion to table NPRR1256 and refer the issue to WMS added to the combo ballot.
- Introduction of NPRR1256, concerning settlement MRA for energy storage resources.
- This item is being introduced by ERCOT and it is the first time it is being discussed at PRS.
- No representative from ERCOT present to speak on the proposal.
- Consideration to table and refer the item for further review.
- Suggestion for PRS and WMS to examine and verify the proposal.
- The item relates to protocol language updates needed for energy storage resources.
- Current protocols use generation resource language which needs adaptation for the integration of energy storage resources as a single model.
- Potential updates to MRA language to reference generation resources or energy storage resources.
- Mathematical validations required, possibly by WMS.
7.2 – NPRR1257, Limit on Amount of RRS a Resource can Provide Using Primary Frequency Response
- Motion to table NPRR1257 and refer the issue to ROS added to the combo ballot.
- This proposal originated from recommendations by a consultant, GE, to address the risk of common mode failure, which could lead to NERC requirements violations.
- A static limit derived from studies conducted by ERCOT is proposed, with a recommended limit of 157 megawatts per resource.
- The limit applies per resource and not per station, with each resource expected to have independent controls to mitigate risks from common mode failures.
- There are companion NOGRR documents providing detailed application instructions for the proposed limit.
- Some concerns were raised on regulatory certainty and changeability of the limit number, but these were addressed collaboratively with ERCOT.
- Questions were raised regarding the application of the limit: 20% of HSL or 157 megawatts for thermal resources, and verified droop performance for batteries.
- Recommendation to table this NPRR for further discussion and consideration by the ROS and PDCWG.
7.3 – NPRR1258, TSP Performance Monitoring Update
- Motion to recommend approval of NPRR1258 as submitted added to the combo ballot.
- Removal of duplicative language in section 8.3 and section 3.
- Clarification on requirements for submissions to ERCOT via the common information model to follow a defined naming convention.
- The submission system automatically rejects non-compliant naming conventions, reducing the need for additional performance monitoring.
- Monitoring program viewed as redundant and potentially pose compliance risks.
7.4 – NPRR1259, Update Section 15 Level Response Language
- Motion to table NPRR1259 and refer the issue to RMS added to the combo ballot.
- Clarification that retail transaction response timing requirements are not included for planned and approved retail system outages.
- Consideration to table and refer the item to RMS for further review.
- Discussion on the need for additional clarification on approval by the TAC Subcommittee regarding ERCOT planned outages.
8 – Other Business – Diana Coleman
- Discussed possibility of not having PRS meeting in December as there will not be a December TAC meeting
- January PRS meeting is scheduled prior to the TAC meeting.
- NPRR1151 allows cancellation of monthly PRS meetings.
- Concern raised about skipping the December meeting as new NPRRs are available for discussion.
- If December meeting is skipped, certain NPRRs would be delayed to future meetings.
- Productivity noted with end-of-year NPRRs and filing deadlines approaching.
- Suggestion to consider using Webex or alternate options for December meeting if needed.
9 – Combo Ballot – Vote – Diana Coleman
- Motion to approve combo ballot carries unanimously